Definition(s)


Class I, Division 1 Location

A Class I, Division 1 location is a location: 1) in which ignitable concentrations of flammable gases or vapors exist continuously, intermittently, or periodically under normal operating conditions; or 2) in which ignitable concentration of such gases or vapors may exist frequently because of repair or maintenance operations or because of leakage; or 3) in which breakdown or faulty operation of equipment or processes might release ignitable concentrations of flammable gases or vapors, and might also cause simultaneous failure of electrical equipment (see NEC Article 500 and API 500).

Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards

Class I, Division 1 Location

A location in which ignitable concentrations of flammable gases or vapors are expected to exist under normal operating conditions or in which faulty operation of equipment or processes might simultaneously release flammable gases or vapors and also cause failure of electrical equipment. Reference 6.2.1.1.a and NEC Article 500.5(B)(1) for a more complete definition.

API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, Third Edition, December 2012, Global Standards